Bently 2300/20 and 2300/25 2300 Vibration Monitors
The 2300 Vibration Monitors provide cost-effective continuous vibration monitoring and protection capabilities for less critical and spared machinery. They are specifically designed to continuously monitor and protect essential medium to low criticality machinery in a wide range of industries including: oil & gas, power generation, water treatment, pulp and paper, manufacturing, mining, cement, and other industries.
The 2300 Vibration Monitors deliver vibration monitoring and high vibration level alarming. They include two channels of seismic or proximity measurement inputs from various accelerometer, Velomitor and Proximitor types, a speed input channel for time-synchronous measurements, and outputs for relay contacts. The 2300/20 monitor features a configurable 4-20 mA output which interfaces more points to a DCS. The 2300/25 monitor features System 1 Classic connectivity for Trendmaster SPA interface which enables users to leverage existing DSM SPA infrastructure.
The 2300 Vibration Monitors are designed for using on a broad range of machine trains or individual casings where the sensor point count fits the monitor’s channel count and where advanced signal processing is desired.
2300/20
l
Two 4-20 mA outputs with internal current loop power supply.
l
Continuous monitoring and protection
l
Two acceleration/velocity/proximity inputs with synchronized sampling for advanced diagnostics.
l
One dedicated speed channel supporting Proximity probes, Magnetic pickup and Proximity switch type sensors.
l
Supports process variable on all three input channels.
l
Key measurements (Acceleration pk, Acceleration rms, Velocity pk, Velocity rms, Displacement pp, Displacement rms, Speed) real-time provided with alarm configuration.
l
Each channel has one measurement group, and can add additional two bandpass measurements and several nX measurements (depends on the device availability).
l
LCD and LED for real time value and status display.
l
Ethernet 10/100 Base-T communication for configuration using Bently Nevada Monitor Configuration software (Included) with RSA encryption.
l
Local contacts for positive engagement of monitor bypass, configuration lockout, and latched alarm/relay reset.
l
Two relay outputs with programmable setpoints.
l
Three buffered transducer outputs (including Keyphasor signal) providing short circuit and EMI protection. Buffered outputs for each signal are through BNC connectors.
l
Modbus over Ethernet.
l
Alarm Data Capture
2300/25
l
Trendmaster SPA interface.
l
Continuous monitoring and protection.
l
Two Acceleration/Velocity/Proximity inputs with synchronized sampling for advanced diagnostics.
l
One dedicated speed channel supporting Proximity probes, Magnetic pickup and Proixmity switch type sensor.
l
Support process variable on all three input channels.
l
Key measurements (Acceleration pk, Acceleration rms, Velocity pk, Velocity rms, Displacement pp, Displacement rms, Speed) real-time provided with alarm configuration.
l
Each channel has one measurement group, and can add additional two bandpass measurements and several nX measurements (depends on the device availability).
l
LCD and LED for real time value and status display.
l
Ethernet 10/100 Base-T communication for configuration using Bently Nevada Monitor Configuration software (included) with RSA encryption.
l
ocal contacts for positive engagement of monitor bypass, configuration lockout, and latched alarm/relay reset.
l
Two relay outputs with programmable setpoints.
l
Three buffered transducer outputs (including Keyphasor signal) providing short circuit and EMI protection. Buffered outputs for each signal are through BNC connectors.
l
Modbus over Ethernet.
l
Alarm Data Capture
DC Input
18~36 Vdc, max 7.5 W
ICP Accelerometers
Configurable Bandpass filter
0.2 Hz to 20 kHz
Scale Factor range
5 to 1000 mV/g
Full scale range
2 to 80 g peak
Current Sink Source
3.3 mA ± 5%
Open Circuit Voltage
-21 to -24 Vdc
Type
Single pole, double throw
Sealing
Epoxy sealed
Contact life
100,000 cycles @ 5 amps250 Vac
200,000 @ 1 amp, 24 Vdc
Insulationresistance
1000 MΩ minimum @ 500 Vdc
Relay closed contact resistance
1 Ω maximum
Relay open contact resistance
1 MΩ minimum
Maximum switched contact voltage
250 Vac / 250 Vdc
Maximum breaking contact current
6 A @250 Vac / 6 A @24 Vdc
Maximum switched power
1500VA AC / 150 Watts DC
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.