BASLER DECS-200-2L Digital Excitation Control System DECS2002L
One DECS-200 Digital Excitation Control System can accommodate 32Vdc, 63Vdc, or
125Vdc applications up to 15Adc. This unique flexibility provides precision control of
generators of virtually any size. The DECS-200 also incorporates a pulse width modulated
power stage, which improves system performances in non-linear load applications.
• True RMS sensing, single or three phase
• 32Vdc, 63Vdc, and 125Vdc outputs at 15Adc
• 0.25% Voltage Regulation Accuracy
• Setup from front panel HMI or by PC with Windows® setup software included
• 20 standard stability selections
• User customizable stability selection
• Paralleling compensation
• Underfrequency compensation or V/Hz Ratio Limiter
• Soft start buildup
• Field Current Regulation Mode (Manual Mode)
• Autotracking between operating modes and between DECS-200 units
(optional)
• Minimum Excitation Limiter (Internally generated or customizable)
• On and off-line Maximum Excitation Limiters
• Stator Current Limiter
• Var and Power Factor Controllers
• Exciter Diode Monitoring (EDM)
• Sequence of Events Recording
• Oscillography
Generator Current Sensing Two ac current sensing ranges and two channel (phase) inputs:
• For metering and control: 1A and 5A.
• For cross current compensation: 1A and 5A.
Sensing Burden Voltage: Less than 1VA per phase.
Current: Less than 1VA.
Parallel Compensation: Less than 1VA.
Contact Switching Inputs 11 contact switching inputs are supplied with 24Vdc to accommodate dry
contacts. Contacts are as follows:
• Start • Var/PF Enable
• Stop • Pre-position
• Secondary DECS Enabled (optional) • Raise Switch
• Unit/Parallel Operation • Lower Switch
• AVR Mode • Alarm Rest
• FCR Mode
Remote Set Point Control Two separate analog inputs for remote set point control. Typically used to accept
(Accessory Input) a signal from a Power System Stabilizer. Select one from the configuration menu.
• ±10Vdc
• 4 to 20 milliamperes
DECS-200-1C
DECS-200-1L
REGULATION ACCURACY
AVR Mode: Voltage regulation equals ±0.25% over the load range at rated power factor and constant
generator frequency. Steady state stability equals ±0.1% at a constant load and generator frequency.
Temperature drift equals ±0.5% for 0 to 50°C temperature change. Underfrequency (volts/hertz)
characteristic slope from 0 to 3.0 P.U. is adjustable in 0.1 P.U. increments.
FCR Mode: Field current regulation equals ±1.0% of the nominal value for 10% of the bridge input voltage
change or 20% of the field resistance change.
var Mode: ±2.0% of the nominal VA rating at the rated frequency.
PF Mode: ±0.02 PF in the set point PF for the real power between 10 and 100% at the rated frequency.
(e.g. -set point PF=0.80, PF regulation is from 0.78 to 0.82 PF.)
Internal autotracking(optional): ±0.5% of the nominal field voltage change when transferring.
PARALLEL COMPENSATION Can use either reactive droop or reactive differential (cross-current) compensation.
Adjustable from 0 to 30% of the rated generator voltage droop with optional 1 ampere or less or 5 amperes
or less input. Line drop compensation uses this same parameter; however, it is adjustable from -30% to 0.
FIELD OVERVOLTAGE PROTECTION Adjustable in increments of 1.0Vdc from 1.0 to 325Vdc rated output
voltage with a 0.2 to a 0.2 to 30 second inverse time delay settable in increments of 0.1 second.
FIELD OVERCURRENT PROTECTION Adjustable in increments of 0.1Adc steps of rated field current from 0 to
16Adc excitation current setting with an inverse time delay (ANSI C50.13).
EXCITER DIODE MONITOR (EDM) The DECS-200's EDM can detect open and shorted diodes on brushless
generators. To do this, the DECS-200 requires the user to input the number of generator poles and the number of
exciter poles (both adjustable from 0 to 20 in increments of 2). The open and shorted diode ripple threshold is
adjustable from 0 to 100% of field current. The open diode protection time delay is adjustable from 10 to 60
seconds, and the shorted diode protection time delay is adjustable from 5 to 30 seconds.
GENERATOR UNDERVOLTAGE PROTECTION Adjustable in increments of 1Vac from 0 to 30kV sensing voltage
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.