ABB SPAU 341 C Voltage regulator SPAU341C How to set it up?
The voltage regulator SPAU 341 C is intended
to be used for regulating the voltage of power
transformers with on-load tap-changers in distribution
substations. The connections required
for a simple voltage regulating function is the
measured phase-to-phase voltage U12 and the
raise and lower output contacts. If the line drop
compensation, the minimizing circulating current
or the overcurrent blocking feature is to be
used, one or more phase currents have to be
measured. If only one phase current is measured,
it is always connected to the terminals of
the phase current I L1, and the current to be
measured is selected with the software switches
SGF2/6 and SGF2/7 of the automatic voltage
regulating module SPCU 1D50.
The purpose of the regulator is to maintain a
stable secondary voltage of the power transformer.
The basis for this operation is the reference
voltage, which is set by the user. By adding
or decreasing various compensation factors, the
regulator calculates a control voltage from the
reference voltage. Hence, the control voltage is
the desired transformer secondary voltage to be
maintained by the regulator. Then the control
voltage is compared with the voltage measured
and the difference between these two forms the
regulating process error.
Since the tap-changer changes the voltage in
steps, a certain error has to be allowed. This error,
called bandwidth, is also set by the user. If
the measured voltage fluctuates within the bandwidth,
the regulator is inactive. Should, on the
other hand, the measured voltage be outside
these bandwidth limits, an adjustable delay T1
starts. This delay T1 remains active as long as
the measured voltage is outside the hysteresis
limits of the bandwidth. The factory setting of
the hysteresis limits is 90%.
Should the measured voltage still be outside the
hysteresis, when the delay counter T1 reaches
its setting value, the raise or lower output relay
is activated and the motor drive of the tapchanger
is operated. If, on the other hand, the
measured voltage falls within the hysteresis limits,
the delay counter is reset.
Should one tap-changer operation not be
enough to regulate the transformer voltage
within the hysteresis limits, a second adjustable
delay T2, usually with a shorter time setting than
T1, starts.
The delays T1 and T2 can be selected either
with definite or inverse time characteristic. Inverse
time characteristic means, that the delay
is inversely proportional to the regulator error,
i.e the delay is inversely proportional to the difference
between the control voltage and the
measured voltage.
The voltage regulating function will be described
more in detail in the document 1MRS 750111-
MUM EN.
Block Blocking of regulating function, input
Uaux Auxiliary voltage, input
RSV Reduce set voltage or parallel input
AUT/MAN Automatic or manual mode, output
IRF Self-supervision signal, output
RAISE Raise signal, output
LOWER Lower signal, output
I> Overcurrent or overvoltage blocking, output
U< Undervoltage blocking output
SERIAL PORT Serial communication port
TAP POS Tap-changer position input, mA signal
TCO Tap-changer operating input
RAISE' Raise command or parallel operation input
LOWER' Lower command or reduce set voltage input
AUTO' Automatic mode input
MAN' Manual mode input
U1 Automatic voltage regulating module SPCU 1D50
U2 Manual voltage regulating module SPCN 1D56
U5 I/O module
U6 Energizing input module
SPA-ZC_ Bus connection module
Rx/Tx Fibre-optic receiver (Rx) and transmitter (Tx) of the bus connection module
The power supply module is located behind the
system front panel of the regulator and can be
withdrawn after removal of the system front
panel. The power supply module produces the
voltages required by the regulating modules
from the auxiliary voltage.
There are two types of power supply modules,
differing only in input voltage:
SPGU 240 A1:
Rated voltage Un = 110/120/230/240 V ac
Un = 110/125/220 V dc
Operative range U = 80…265 V ac/dc
SPGU 48 B2:
Rated voltage Un = 24/48/60 V dc
Operative range U = 18…80 V dc
Which power supply the regulator contains, is
marked on the system panel.
The power supply module is a transformer-connected,
i. e. galvanically separated primary and
secondary circuits, flyback type rectifier. The
primary circuit is protected by a 1 A fuse, F1
(slow), in SPGU 240 A1, and a 4 A fuse (fast)
in SPGU 48 B2. The fuses are located on the
circuit board of the module.
When the power supply module is operating,
the green LED indicator Uaux on the system
panel is lit. The supervision of the supply
voltages for the electronics is incorporated into
the regulating modules. A self-supervision alarm
is given if one of the secondary voltages differs
by more than 25% from the rated value. An
alarm signal is also obtained, if the power supply
module is missing, or if the auxiliary voltage
to the regulator has been interrupted.
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.
COPYRIGHT© 2003-2025 Copyrighted
Phone(WeChat/Whatsapp)
+086-181 4410 0983
No 1134 Jimei North Road,
Hong Kong Office:
Guan Tang District, Hong Kong,