ABB Symphony Plus S+ Turbine: Auto Synchronizer Module AS800
The Auto Synchronizer AS800 provides automatic breaker
closure during generator to line synchronization or during peer
to peer bus synchronization in switchyard applications. The
AS800 is also capable of detecting a dead bus to initiate safe
breaker closure from a live bus to a de-energized bus. The
AS800 may be installed in centralized or remote locations. The
AS800 integrates into DCS systems or operates standalone.
Communication to the module is accomplished through the
on-board Profibus interface for DCS operation or through a
serial interface for standalone configuration. Monitoring and
configuration are available via either of these communication
ports
Property Characteristic/Value
Electrical
Supply voltage +24VDC +/-5%
Operating Current 264 mA Typical
Power consumption 6.4 W Typical
Field I/O +24VDC (fused @ ¼ amp)
ROM810v2 (no field I/O) +24VDC +/-5% @ 0.02 A typical de-energized (both coils)
+24VDC +/-5% @ 0.17 A typical energized (both coils)
Operating
Low Voltage (LV1-6) Up to 48 V
High Voltage (HV1-2) Up to 150 VAC/VDC
Digital Inputs (DI1-2) Up to 150 VAC/VDC
Digital Outputs (DO1-6) Dry Relay Contact (2-Form C), 3 A @ 150 VDC / 5 A @ 120 VAC
Performance
Analog Input Voltage 1 % of full scale
Analog Input Frequency +/- 0.01 Hz
Phase Difference +/- 0.1 degrees
Property Characteristic/Value
Environmental
CE Mark (when installed in a cabinet)
EMC96 Directive (89/336/EEC)
Low Voltage Directive (73/23/EEC)
EN50082-2 Part 2
EN61010-1 Part 1
CSA certification (non-hazardous location)
Ambient Temperature 0° to 55° C (32° to 131° F)
Humidity 5 % to 90 % RH (±5 %) up to 55°C (non condensing)
5 % to 40 % RH (±5 %) up to 70°C (non-condensing)
Atmospheric Pressure Sea level to 3 km (1.86 miles)
Air Quality Non-corrosive
Installation Category Category II per ANSI/ISA-S82.01-1994
General
Dimensions 123 mm width, 186 mm height, 122 mm depth
4.84 in. width, 7.32 in. height, 4.8 in. depth
Microprocessors MCF5272 with 16 MB Flash, 25 MHz, 16 MB DRAM
ATmega8535 @ 8 MHz, with 8 KB Flash, 512 Bytes SRAM, 512 Bytes EEPROM
System Communications Profibus DP
Module Mounting Each module occupies one slot in a Termination Base Unit (TBU810)
I/O Termination Termination Base Unit (TBU810)
TBU810 Cabinet Mounting Standard 35 mm DIN Rail
TU Terminal Blocks
24 A / 250 V Compression 0.2–4 mm2 [solid] /
0.2–2.5 mm2 [stranded] /
24–12 AWG
CPM810 ASM810
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.