List of cross references for the basic units of the 40/50 series
An exchange of MODBUS data is realized in a table defined by: - the MODBUS address of the first exchanged variable - the list size = the total number of variables in the list.
All of the variables of the series 40/50 basic units can, as described in the tables on the following pages, be read or written by the master MODBUS.
- MODBUS addressing method:
VAR 00.00→→→→→→→→→→→→→→→→→→→→→ADDR 0
(VAR = Typ I,O,S,M,IW,OW,MW,KW) (Address of the first selected variable,in decimal)
VAR XX.YY = ADDR 0 + ( 16 * XX ) + YY
(VAR = Typ MD,KD) (Address of the first selected variable, in decimal)
VAR XX.YY = ADDR 0 + ( 32 * XX ) + ( 2 * YY )
Example: Find the MODBUS address of the variables O62.15 and M232.01 and MD002.07
O 62.15 = 4096 + ( 16 * 62 ) + 15 = 5103
M 232.01 = 8192 + ( 16 * 232 ) + 1 = 11905
MD002.07 = 4000 + ( 32 * 2 ) + ( 2 * 7 ) = 16462
IMDS003
IMDS014
IMDSM04
IMDSO14
IMFEC12
IMHSS03
IMMPI01
IMSET01
INNIS01
INNIS21
INNPM12
INSEM01
IOR810
-K01 3BSE084740R1
KUC720AE
LDGRB-01
LIMELITE 2000
LT8978bV1
LXN1604-6
M063B
M2004HW
MB510
MP3-11W
MSR04X1
MSR04XI
MVR 0.44-10KA
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.
COPYRIGHT© 2003-2024 Copyrighted
Phone(WeChat/Whatsapp)
+086-18144100983
No 1134 Jimei North Road, Jimei District
Hong Kong Office:
Guan Tang District, Hong Kong,