ANALOG CURRENT INPUTS
Current Inputs: 0 to 1 mA, 0 to 20 mA, 4 to 20mA
(setpoint)
Input Impedance: 226 Ω ±10%
Conversion Range: 0 to 2 mA
Accuracy: ±1% of full scale
Type: Passive
Analog Input Supply: +24 V DC at 100 mA max.
Sampling Interval: 50 ms
COMMUNICATIONS PORTS
RS232 Port: 1, Front Panel, non-isolated
RS485 Ports: 2, Isolated together at 36 Vpk
RS485 Baud Rates: 300, 1200, 2400, 4800, 9600, 19200
RS232 Baud Rate: 9600
Parity: None, Odd, Even
Protocol: Modbus® RTU / half duplex, DNP 3.0
ANALOG CURRENT OUTPUT
Type: Active
Range: 4 to 20mA, 0 to 1 mA
(must be specified with order)
Accuracy: ±1% of full scale
4 to 20 mA max. load: 1.2 kΩ
0 to 1mA max. load: 10 kΩ
Isolation: 36 Vpk
(isolated with RTDs and analog inputs)
4 Assignable Outputs: Phase A, B, C output current
3 phase average current
negative sequence current
generator load
hottest stator RTD
hottest bearing RTD
RTD # 1 to 12
AB voltage
BC voltage
CA voltage
average phase-phase voltage
volts/hertz
frequency
3rd harmonic neutral voltage
power factor
3 phase reactive power (Mvar)
3 phase real power (MW)
3 phase apparent power (MVA)
analog inputs 1 to 4
tachometer
thermal capacity used
I, Mvar, M
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.