An electronic type designation ID in each module keeps the I/O module from being
taken into operation by the ModuleBus master, if a module’s ID doesn’t match the
configured module type definition.
Refer to specifications in Appendix A, Specifications for more information.
The module can be mounted on a standard DIN rail. The module is locked to the
DIN rail by using the locking screw.
The process connection is done via detachable connectors.
AI801 Analog Input Module, 0...20 mA
The AI801 Analog Input Module has 8 current inputs.
The current input is able to handle a short circuit to the transmitter supply without
damage. The input withstands HART communication.
Nominal input ranges are: 0(4)... +20 mA.
AO801 Analog Output Module, 0...20 mA
The AO801 Analog Output Module has 8 current outputs. State of outputs can be
set to a predetermined (OSP) value if a communications error is detected. Nominal
output range is: 0(4)... 20 mA.
DI801 Digital Input Module, 24 V, Current Sinking
The DI801 Digital Input Module has 16 channels for 24 volt d.c. digital inputs.
One input channel can be used for sensor voltage supervision. Each input channel
provides current limiting, EMC protection, input state LED indicator and optical
isolation from the ModuleBus.
DI802 Digital Input Module, 120 V a.c./d.c., Current Sinking
The DI802 Digital Input Module has 8 channels for 120 volt a.c./d.c. digital inputs.
Channel 8 can be used for sensor voltage supervision. Each input channel provides
current limiting, EMC protection, input state LED indicator and optical isolation
from the ModuleBus.
DI803 Digital Input Module, 230 V a.c./d.c., Current Sinking
The DI803 Digital Input Module has 8 channels for 230 volt a.c./d.c. digital inputs.
Channel 8 can be used for sensor voltage supervision. Each input channel provides
current limiting, EMC protection, input state LED indicator and optical isolation
from the ModuleBus.
DO801 Digital Output Module, 24 V, 0.5 V, Current Sinking
The DO801 Digital Output Module has 16 channels for 24 volt d.c., 0.5 A, digital
outputs. Each output channel provides protection against short circuits to ground,
over-voltage, over-temperature, EMC protection, output state LED indicator and
optical isolation from the ModuleBus. State of outputs can be set to a predetermined
(OSP) value if a communications lost error is detected.
DO802 Digital Output Module, 24-250 V, Relay Normally Open
The DO802 Digital Output Module has 8 channels for 24-250 volt d.c., digital
outputs. Each output channel provides protection against short circuits to ground,
over-voltage, over-temperature, EMC protection, output state LED indicator and
optical isolation from the ModuleBus. State of outputs can be set to a predetermined
(OSP) value if a communications lost error is detected.
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.