Type EHDB
• 220 amps to 960 amps
• 2 pole (2 N.O.) and 3 pole (2 N.O. & 1 N.C.) power poles available
• 600 VDC making capacity: 300 VDC breaking capacity
• 1 N.O. & 1 N.C. auxiliary contacts are standard and up to six additional auxiliary contacts may be added to provide a total of 8 (4 N.O. & 4 N.C.)
• Early make & late break auxiliary contacts available
• Auxiliary contacts available to meet elevator standards
• EHDB 220, 280 & 360 contactors have withdrawable coils
• Mechanically interlocked contactors available for reversing applications
• Double break contact design with magnetic arc chamber extinguishes arc in shortest possible time
• High temperature encapsulated coil
• Easy removal of arc chute for quick inspection and change of contacts
• Operates over an extended voltage range of 85% to 110% of rated control voltage
• DC control operation available
• UL & CSA approved UL File # E36588 CSA File # LR19700
Type DA
• 60 amps size
• 500 volt DC ratings
• 160 and 300 volt DC normal closed ratings for dynamic braking
• Low energy auxiliary contacts available (17V, 5mA)
• Mechanically interlocked version available for reversing applications
• Small compact design • 2 pole (2 N.O.) and 3 pole (2 N.O. & 1 N.C.) available
• Additional auxiliary contact blocks available
• Auxiliary contacts available to meet elevator standards
• Fast, snap-on DIN rail mounting
• Double break contact design
• Captive terminal screws
• Touch-safe design: all connection terminals are protected against accidental touch
• Terminals supplied open for ease of wiring
• Operates over an extended voltage range of 85% to 110% of rated control voltage
• N.C. dynamic braking pole is easily added to two pole contactors
• Screwdriver guide holes
• Snap-on front mounted accessories
• UL and CSA approved
Description
EHDB drive contactors are specifically designed for use with solid state D.C. adjustable speed drive systems. In drive applications, the contactor is not required to make or break the load during normal operation. The N.C. contact is used for dynamic braking applications. EHDB contactors are provided less terminal lugs.
DC operated contactors
EHDB220 – EHDB960
DC and AC operated contactors have the same magnet structure except the DC coil includes a resistor and a normally closed late break auxiliary interlock. To order, substitute the code from the coil voltage selection chart and refer to the DC magnet coils chart for the price adder. DC operated contactors are supplied with 2 N.O. & 1 N.C. auxiliary contacts. One additional 1 N.O. & 1 N.C. auxiliary contact block can be mounted on the left side of the contactor.
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.