General
System communications
8 bit parallel
Speed signal resolution
Accuracy
0 - 1000RPM
1000 - 12000RPM
12000 - 20000RPM
Mounting
One slot in standard Symphony Plus Modular Mounting Unit
I/O termination
Turbine Protection System Termination Unit (TPSTU02)
NTDI01 for TSA01 and FCS01 modes
Operating
Speed probe input
0.5–20 kHz, 0.05–120 VAC
Analog input
4–20 mA or 1–5 VDC (field inputs from termination unit)
Analog output
4–20 mA or 1–5 VDC (field outputs to termination unit)
Digital input
24 VDC (field inputs from termination unit)
(24–125 VDC, or 24–120 VAC converted on TPSTU02 termination unit).
120 VAC/125 VDC for TSA01
Digital output
24 VDC (to termination unit) for TPS02, 120 VAC/125 VDC for TSA01
Electrical
Operating voltage
+15 VDC ±5% at 320 mA +5 VDC ±5% at 100 mA
+24 VDC ±10% at 75 mA
Power dissipation
4.8 W @ +15 VDC 0.5 W @ +5 VDC
1.8 W @ +24 VDC
Environmental
Electromagnetic/radio
frequency interference
Values not available at this time. Keep cabinet doors closed. Do not use communications equipment any closer than two meters from the cabinet.
Ambient temperature
0° to 70° C (32° to 158° F)
Humidity
5% to 90% RH (±5%) up to 55°C (non-condensing)
5% to 40% RH (±5%) up to 70°C (non-condensing)
Atmospheric pressure
Seal level to 3 km (1.86 miles)
STPPS13FCS SPTPS13TPS
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.