Proven Technology
• Field proven solution, delivering online DGA
solutions for over 40 years
• Over 50,000 Hydran units sold worldwide
• Estimated sensor life in excess of 10 years*
Expandable
• Compatible with various transformer oil types
(standard mineral insulating oils and newer
natural and synthetic ester based fluids)
• Available with the traditional Hydran
composite gas (H2, CO, C₂H₂, C₂H₄) sensor or
with a discrete Hydrogen only (H2) sensor
• Easily upgradable in the field to accept
analogue signals to monitor other key
transformer parameters
• Computation of winding hot spot and other
IEEE transformer models for enhanced
diagnostics of the transformer’s condition
(depending on sensors installed)
• Integrates with Kelman multi-gas DGA devices
Intuitive
• Easy to install on a single existing transformer
valve, often without an outage required
• Integrated display and keypad for simplified
local user interaction and data visualization
• Built-in moisture sensor provides water in oil
measurement, critical to identifying paper
degradation and leaking gaskets
• Compatible with GE’s acclaimed Perception™
software to download, trend and analyze
transformer health data
Enhanced Monitoring with Extended Sensor Life
When a transformer’s insulation system is overstressed, the oil and paper undergo chemical
degradation producing both hydro-carbon gases and moisture that dissolve into the insulating oil. This
increased ageing will shorten the transformer’s life, impact its reliability and in some cases can even
lead to catastrophic failures.
The Hydran M2-X is the next generation of the field-proven family of Hydran DGA monitoring solutions.
It provides continuous monitoring of gas and moisture levels to alert users of developing faults and
minimize the risk of unplanned outages. The M2-X builds on GE’s strong domain expertise to deliver an
optimized, low maintenance monitoring device with an extended sensor life.
Key Benefits
• Small form factor, no moving parts, low maintenance, and support for APM software analytics,
enabling fleet level deployments
• Condition monitoring for a wide range of transformers with mineral insulating oils or ester based
fluids (natural and synthetic)
• Extending beyond DGA monitoring, through the connection of sensors, the Hydran M2-X can monitor
other parameters such as top oil temperature, load current and through the use of IEEE based
mathematical models, can provide further insight on changing transformer conditions
• Providing critical transformer gas behavior data for Asset Performance Management (APM)
strategies, facilitating planning of site intervention and maintenance activities
• Supports a wide range of communication methods and protocols to enable easy and secure
integration with GE's digital platforms including Perception™ transformer fleet management
software, DS Agile substation HMI, PREDIX™, and other APM software tools, historians and SCADA
systems
Applications
Advanced, flexible and expandable DGA monitoring solution tailored for utility and industrial
transformers.
Easily integrates with Kelman multi-gas DGA devices and the Multilin 845 protection & control
relay to provide continuous synchronization of chemical and electrical measurements for enhanced
transformer monitoring.
MEASUREMENTS
Fuel cell type sensor behind a gas permeable membrane in
contact with transformer insulating oil
Range 25-2000 ppm (volume/volume H₂
equivalent)
Accuracy** ±10% of reading ±25 ppm
Response time 10 minutes (90% of step change)
"Composite Gas" Sensor
Relative sensitivity H₂: 100% of concentration
CO: 15 ± 4 % of concentration
C₂H₂: 8 ± 2 % of concentration
C₂H₄: 1.5 ± 0.5 % of concentration
Repeatability highest of ±5% of reading or ±5 ppm
"Discrete H2" Gas Sensor (Mineral oil only)
Relative sensitivity H₂: 100% of concentration
Interference from CO, C2H2 and C2H4
less than 3% of concentration
Repeatability highest of ±5% of reading or ±10 ppm
Moisture Sensor
Thin film capacitive type sensor immersed in insulting oil
Range 0-100% RH
Accuracy ± 2% RH
Repeatability ± 2% RH
FEATURES
Display
Backlit LCD, 128 x 64 pixels
Keypad to setup unit and acknowledge alarms
Communications
Standard RS-232 port (DB-9 connector), for local connection to
computer for configuring the system
Standard RS-485 (terminal block), isolated to 2000Vac RMS, for
remote communication or connection to local Hydran network
Optional: Ethernet or Fiber Optic over TCP/IP
Protocols
Standard: Modbus®, DNP 3.0
Optional: IEC 61850 over TCP/IP
Alarms
Gas and Moisture Alert (Hi), Gas and Moisture Alarm (HiHi),
System Alarms
Gas alarms can be set on gas level reached or on hourly or daily
trend (gas level rate of change)
Moisture alarms can be set on level reached or average level
Alarms can also be configured for optional additional analogue
inputs or for calculation results from optional transformer models
5 dry contact relays (type C, SPDT), NO/NC, 3A@250Vac resistive
load, 3A@30Vdc resistive load
Manual Sampling
Easily accessible external oil sampling port, for use with glass
syringe with Luer stopcock
ENVIRONMENT
Conditions
Operating ambient
temperature
-40°C to +55°C (-40°F to +131°F)
Operating ambient
humidity
0-95% RH, non-condensing
Oil temperature at
valve
-40°C to +105°C (-40°F to +221°F) with
finned heat sink adapter option
Oil pressure at valve 0-700KPa (0-100psi)
Vacuum resistant sensor
Enclosure Rating
NEMA Type 4X certified, meets requirements of IP56
Power Requirements
90–132 Vac or 180–264 Vac switch mode universal power supply,
47–63 Hz, 650VA max
Mechanical
Has a 1.5” NPT male thread, can mount on 1.5” NPT valve or
greater using optional adapters
Dimensions 315 x 219 x 196 mm
12.4 x 8.63 x 7.72 "
Installed weight 7.5Kg (16.5lb)
Shipping weight 9.0Kg (20lb)
PRODUCT OPTIONS & SENSORS
Finned heat sink adapter (1.5”) for use when ambient temp >
40°C (104°F) or oil temp > 90°C (194°F).
Valve adaptors 2” to 1.5”
Transformer models calculations (for mineral oil only)
Analogue input cards, 4-20mA, 10V load max, isolated to
2000Vac RMS
Dual digital input cards for dry contacts, internal wetting 24Vdc,
isolated 2000Vac
Analogue output cards, 4-20mA, 10V load max, isolated to
2000Vac RMS
PSTN analogue modem V92/56K
GSM/GPRS wireless modem
Network Ethernet communication using copper (RJ-45) or
multimode fiber optic (ST)
Oil temperature sensor, magnetic mount, (4-20mA)
Split core load CT (4-20mA)
Ambient temperature sensor (4-20mA)
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.