fluids (natural and synthetic)
• Extending beyond DGA monitoring, through the connection of sensors, the Hydran M2-X can monitor
other parameters such as top oil temperature, load current and through the use of IEEE based
mathematical models, can provide further insight on changing transformer conditions
• Providing critical transformer gas behavior data for Asset Performance Management (APM)
strategies, facilitating planning of site intervention and maintenance activities
• Supports a wide range of communication methods and protocols to enable easy and secure
integration with GE's digital platforms including Perception™ transformer fleet management
software, DS Agile substation HMI, PREDIX™, and other APM software tools, historians and SCADA
systems
Applications
Advanced, flexible and expandable DGA monitoring solution tailored for utility and industrial
transformers.
Easily integrates with Kelman multi-gas DGA devices and the Multilin 845 protection & control
relay to provide continuous synchronization of chemical and electrical measurements for enhanced
transformer monitoring.
MEASUREMENTS
Fuel cell type sensor behind a gas permeable membrane in
contact with transformer insulating oil
Range 25-2000 ppm (volume/volume H₂
equivalent)
Accuracy** ±10% of reading ±25 ppm
Response time 10 minutes (90% of step change)
"Composite Gas" Sensor
Relative sensitivity H₂: 100% of concentration
CO: 15 ± 4 % of concentration
C₂H₂: 8 ± 2 % of concentration
C₂H₄: 1.5 ± 0.5 % of concentration
Repeatability highest of ±5% of reading or ±5 ppm
"Discrete H2" Gas Sensor (Mineral oil only)
Relative sensitivity H₂: 100% of concentration
Interference from CO, C2H2 and C2H4
less than 3% of concentration
Repeatability highest of ±5% of reading or ±10 ppm
Moisture Sensor
Thin film capacitive type sensor immersed in insulting oil
Range 0-100% RH
Accuracy ± 2% RH
Repeatability ± 2% RH
FEATURES
Display
Backlit LCD, 128 x 64 pixels
Keypad to setup unit and acknowledge alarms
Communications
Standard RS-232 port (DB-9 connector), for local connection to
computer for configuring the system
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.