providing additional system functions.
I/O modules in a ControlLogix system can be owned by a Logix5000™
controller. An owner-controller fulfills these functions:
• Stores configuration data for every module that it owns
• Sends I/O modules configuration data to define module behavior and
begin module operation with the control system
• Resides in a local or remote chassis in regard to the I/O module position
Each ControlLogix I/O module must continuously maintain communication
with its owner-controller to operate normally.
Typically, each module in the system has only one owner-controller. Input
modules can have more than one owner-controller. Output modules, however,
are limited to a single owner-controller.
1756-IA8D, 1756-IA16, 1756-IA16I, 1756-IA32, 1756-IB16, 1756-IB16D, 1756-IB16I, 1756-IB16IF,
1756-IB32, 1756-IC16, 1756-IG16, 1756-IH16I, 1756-IM16I, 1756-IN16, 1756-IV16, 1756-IV32, 1756-OA8, 1756-OA8D,
1756-OA8E, 1756-OA16, 1756-OA16I, 1756-OB8, 1756-OB8EI, 1756-OB8I, 1756-OB16D, 1756-OB16E, 1756-OB16I,
1756-OB16IEF, 1756-OB16IEFS, 1756-OB16IS, 1756-OB32, 1756-OC8, 1756-OG16, 1756-OH8I, 1756-ON8, 1756-OV16E,
1756-OV32E, 1756-OW16I, 1756-OX8I
ControlLogix modules mount in a ControlLogix chassis and require either a
removable terminal block (RTB) or a Bulletin 1492 wiring interface module
(IFM)(1) to connect all field-side wiring.
Before you install and use your module, you must do the following:
• Install and ground a 1756 chassis and power supply. To install these
products, refer to the publications listed in
• Order and receive an RTB or IFM and its components for your
application.
1756-IA8D 79…132V AC 8-point diagnostic input module
1756-IA16 74…132V AC 16-point input module
1756-IA16I 79…132V AC 16-point isolated input module
1756-IA32 74…132V AC 32-point input module
1756-IB16 10…31.2V DC 16-point input module
1756-IB16D 10…30V DC diagnostic input module
1756-IB16I 10…30V DC 16-point, isolated input module
1756-IB16IF 10…30V DC,16-point, isolated, fast peer control input module
1756-IB32 10…31.2V DC 32-point input module
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.