Triconex 通信接口模块 (TCMI) 4351A B
Triconex Communication Interface Module (TCMI)
The TCMI is a standard Honeywell product that provides interface between the Fault Tolerant Ethernet (FTE)
based Enhanced Universal Control Network (EUCN) and Triconex TRICON Safety Manager System.
The TCMI is a redundant device capable of:
• Bi-directional communication with Triconex systems 10.3 and above.
• Execution of data mapping of TRICON memory tables to EUCN format
• Data conversion to EUCN data types (Tag. Parameter), engineering unit and EUCN communication
functions.
• Execution of read and write function to TRICON memory tables
• Definition of signal alarm conditioning and messaging on the EUCN for alarm handling, annunciation
and diagnostic status reporting
• Direct peer-to-peer communication with other EUCN connected devices as Enhanced HighPerformance Process Managers (EHPM), Enhanced Logic Managers (ELMM) or Honeywell Safety
Manager (SM)
• Communication with operators, engineers, and maintenance personnel at the Universal Stations, EST & ESVT via ENIM.
• Support of higher level strategies through communication with Application Modules and host
computers on the Local Control Network via ENIM.
• Database restoration of TCMI Module from the History Module via ENIM.
• Available in two hardware mounting form, front and rear cabinet access mounting (MC-ZTCMIR or
MC-TCMIR1), Front only cabinet access mounting (MC-ZTCMI2 or MC-TCMIR2)
The TCMI connects directly to an Ethernet port of the Tricon Communication Module (TCM) in the Tricon
Safety Manager. The TCM implements the TSAA communication protocol on Ethernet networks for
communication with the Tricon controller. TSAA Protocol is a messaging protocol used in application programs
that read and write data to the Triconex controllers and is utilized by the TCMI.
The TCMI requires the use of a pair (two; one-part number 4351A and one part number 4351B) of TCMs in
the Triconex system. The TCMs connecting to the TCMI must reside in a single Triconex System logical slot
and shall occupy the left and right module physical slots (which comprise a single logical slot). At least 1 port
on each of the TCMs is required to configure a redundant TCMI pair. If empty ports are not available in existing
installed TCMs, then new TCMs must be installed.
Note: Up to four logical slots can be configured for TCMs. Matched pairs of TCMs can be installed in the left
and right positions of each logical slot.
For detailed specifications and technical data on the Triconex TRICON™ version 10.3 and version 11.x system
and TCM interface hardware, please refer to Triconex documentation
3664
4329
3805E
3700A
3002
8312
3636R
3623T
3721
MP6004
CE3008
CE3007
3607E
3481
3604E
3503E
3101
MP2101
3005
3351
3008
3625
HCU3700/3703E
9563-810
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.
COPYRIGHT© 2003-2024 Copyrighted
Phone(WeChat/Whatsapp)
+086-18144100983
No 1134 Jimei North Road, Jimei District
Hong Kong Office:
Guan Tang District, Hong Kong,