ABB Transformer protection IED RET 670 RET670
• A protection, control, and monitoring IED with extensive functional library and configuration possibilities and expandable hardware design to meet specific user requirements
• For power transformers, autotransformers, shunt reactors, T-protection, generator transformer blocks, phase shifting transformers and small busbar systems
• For two- and three-winding transformers with up to six stabilized inputs
• For multi- or single-breaker arrangements
• Transformer differential protection with: - Percentage bias restraint for through faults - Waveform and Second harmonic restraint for transformer inrush - Fifth harmonic restraint for overexcitation - High sensitivity for interturn faults
• Restricted earth fault protection for all direct or low impedance earthed windings - Extremely fast operation - High sensitivity - High and low impedance based
• Full scheme phase-to-phase and phase-to-earth distance protection with up to five zones: - Load encroachment feature
• Instantaneous high speed short circuit function with low transient overreach
• Directional overcurrent protection with four steps for each winding - Each step can be inverse or definite time delayed - Each step can be directional or non-directional
• Instantaneous high speed earth fault function with low transient overreach
• Directional earth fault protection with four stages for each winding
- Each step can be inverse or definite time delayed - Each step can be directional or non-directional - Each step can be blocked on second harmonic component
• Synchrocheck function for single- or multi-breaker arrangements: - Selectable energizing direction - Two functions with built-in voltage selection
• Selectable additional software functions such as breaker failure protection for each breaker, voltage protection, overexcitation protection, control and monitoring
• Tripping from Buchholtz, temperature devices etc. through binary inputs stabilized against capacitive discharges
• Built-in data communication modules for station bus IEC 61850-8-1
• Data communication modules for station bus IEC 60870-5-103, LON and SPA
• Integrated disturbance and event recorder for up to 40 analog and 96 binary signals
• Time synchronization over IEC 61850-8-1, LON, SPA, binary input or with optional GPS module
• Analog measurements accuracy up to below 0.5% for power and 0.25% for current and voltage and with site calibration to optimize total accuracy
• Versatile local human-machine interface
• Extensive self-supervision with internal event recorder
• Six independent groups of complete setting parameters with password protection
• Powerful software PC tool for setting, disturbance evaluation and configuration
• Remote end data communication modules for C37.94 and G.703
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.